Feature



Description

FDJ03FDJ03
5500E015500E01

General description

The Engine Speed Controller ESD5500E is rugged enough to be placed in a control cabinet or engine mounted enclosure with other dedicated control equipment. If water, mist, or condensation may come in contact with controller, it should be mounted vertically. This will allow the fluid to drain away from the speed control unit.

5500E025500E02

TECHNICAL SPECIFICATIONS of ESD5500E Engine Speed Controller

Isochronous Operation/Steady State Stability:

± 0.25% or better

Speed Range/Governor:

1K-7.5K Hz continuous

Speed Drift with Temperature:

± 1% Maximun

IDLE Adjustment:

160 ± 20Hz ~ 60% of set speed

Droop adjustment Min.(K-L Jumpered):

15Hz. ± 6Hz. per 1.0 A change

Droop adjustment Max.(K-L Jumpered):

400Hz. ± 75Hz. per 1.0 A change

Droop Adj. Max. (K-L Jumpered):

875Hz., ± 75Hz. per 1.0 A change

Droop Adj. Min. (K-L Jumpered):

15Hz., ± 6Hz. per 1.0 A change

Speed Trim Range:

± 200Hz.

Remote Variable Speed Range:

500 -7.5Hz. or all part thereof

Terminal Sensitivity:

J: 100Hz., ± 15Hz/Volt @ 5.0 K Impedance

L: 735Hz., ± 60Hz/Volt @ 65 K Impedance

N: 148Hz., ± 10Hz/Volt @ 1Meg. Impedance

P: 10V DC Provide @ 20ma Max.

Speed Switch Adjustment Range:

1000-10000Hz.

5500E035500E03

ENVIRONMENTAL:

Ambient Operating Temperature Range:

-40°c to +85°c

Relative Humidity:

up to 95%

Storage Temperature:

-55°c ~ 90°c

Shock:

20-100HZ 500mm/Sec.

5500E045500E04

INPUT POWER:

Provide:

12 or 24V DC Battery Systems(Transient and Reverse Voltage Protected)

Polarity:

Negative Ground(Case Isolated)

Power Consumption:

50mA continuous plus actuator current

Actuator Current Range @ 25°c-(Inductive Load):

Min. 2.5 Amps, Max. 10 Amps continuous

Speed Sensor Signal

0.5-120 V RMS

Speed Switch Relay Contacts(N.O.and N.C.)

10Amp

Looking for specific info?